Average Service Availability Index

From HandWiki
Revision as of 10:37, 20 July 2022 by imported>TextAI2 (url)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

The Average Service Availability Index (ASAI)[1][2] is a reliability index commonly used by electric power utilities. ASAI is calculated as

[math]\displaystyle{ \mbox{ASAI} = \frac{\sum{N_i} \times 8760 - \sum{U_i N_i}}{\sum{N_i} \times 8760} }[/math]

where [math]\displaystyle{ N_i }[/math] is the number of customers and [math]\displaystyle{ U_i }[/math] is the annual outage time (in hours) for location [math]\displaystyle{ i }[/math]. ASAI can be represented in relation to SAIDI (when the annual SAIDI is given in hours)

[math]\displaystyle{ \mbox{ASAI} = 1 - \frac{\mbox{SAIDI} }{8760} }[/math]

See also

References

  1. Yeddanapudi, Sree. "Distribution System Reliability Evaluation". Iowa State University. Archived from the original on 26 December 2011. https://web.archive.org/web/20111226034249/http://www.ee.iastate.edu/~jdm/ee653/DistributionReliabilityPredictive.ppt. Retrieved 18 June 2011. 
  2. Pham, Hoang (8 April 2003). Handbook of reliability engineering. Birkhäuser. pp. 514. ISBN 978-1-85233-453-6. https://books.google.com/books?id=Xe6Z4wKQFMoC&pg=PA514. Retrieved 21 July 2011.