Engineering:Fire alarm system

From HandWiki
Revision as of 17:31, 4 February 2024 by AnLinks (talk | contribs) (update)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Short description: A system, that works using multiple devices to warn of a fire or other types of emergencies
A fire alarm horn strobe, pull station, and remote annunciator all connected together in a fire alarm system
A fire alarm notification appliance as widely used under North American standards

A fire alarm system is a building system designed to detect and alert occupants and emergency forces of the presence of smoke, fire, carbon monoxide, or other fire-related emergencies. Fire alarm systems are required in most commercial buildings. They may include smoke detectors, heat detectors, and manual fire alarm activation devices, all of which are connected to a Fire Alarm Control Panel (FACP) normally found in an electrical room or panel room. Fire alarm systems generally use visual and audio signalization to warn the occupants of the building. Some fire alarm systems may also disable elevators, which under most circumstances, are unsafe to use during a fire.[1]

Design

After the fire protection is established—usually by referencing the minimum levels of security mandated by the appropriate model building code, insurance agencies, and other authorities—the fire alarm designer will detail specific components, arrangements, and interfaces necessary to accomplish these goals. Equipment specifically manufactured for these purposes is selected, and standardized installation methods are anticipated during the design.

  • ISO 7240-14 is the international standard for the Design, installation, commissioning, and service of fire detection and fire alarm systems in and around the building. This standard was published in August 2013; Status, Published; Edition 1; Technical Committee ISO/TC 21/SC 3 Fire detection and Alarm system.[2]
  • NFPA 72, The National Fire Alarm Code is an established and widely used installation standard from the United States. In Canada, the ULC is the standard for the fire system.

Last version 2019; Status, Published. This code is part of a family standard NFPA

  • TS 54 -14 is a Technical Specification (CEN/TS) for Fire detection and fire alarm system - Part 14: Guidelines for planning, design, installation, commissioning, use, and maintenance. Technical Committee CEN/TC72 has prepared this document, This document is part of the EN 54 series of standards. This standard was published in October 2018; Status, Published.[3]

There are national codes in each European country for planning, design, installation, commissioning, use, and maintenance of fire detection systems with additional requirements that are mentioned on TS 54 -14

Across Oceania, some Standards outline the requirements, test methods, and performance criteria for fire detection control and indicating equipment (FDCIE) utilised in building fire detection and fire alarm systems.

Parts

A fire alarm control panel
Fire alarm speaker and pull station
  • Fire alarm control panel (FACP), or fire alarm control unit (FACU): This component, the hub of the system, monitors inputs and system integrity, controls outputs, and transmits information.
  • Remote Annunciator: a device that connects directly to the panel; the annunciator's main purpose is to allow emergency personnel to view the system status and take command from outside the electrical room the panel is located in. Usually, annunciators are installed by the front door, the door the fire department responds by, or in a fire command center. Annunciators typically have the same commands as the panel's LCD except programming, although some annunciators allow for full system control.
  • Primary power supply: Commonly, a commercial power utility supplies the non-switched 120 or 240-volt alternating current source. A branch circuit is dedicated to the fire alarm system and its constituents in non-residential applications. "Dedicated branch circuits" should not be confused with "Individual branch circuits" which supply energy to a single appliance.
  • Secondary (backup) power supplies: This component, commonly consisting of sealed lead-acid storage batteries or other emergency sources, including generators, is used to supply energy during a primary power failure. The batteries can be either inside the bottom of the panel or inside a separate battery box installed near the panel.
  • Initiating devices: These components act as inputs to the fire alarm control unit and are manually or automatically activated. Examples include pull stations, heat detectors, duct detectors, and smoke detectors. Heat and smoke detectors have different categories of both kinds. Some categories are beam, photoelectric, ionization, aspiration, and duct.
  • Fire alarm notification appliance: This component uses energy supplied from the fire alarm system or other stored energy source, to inform the proximate persons of the need to take action, usually to evacuate. This is done using pulsing incandescent light, flashing strobe light, electromechanical horn, siren, electronic horn, chime, bell, speaker, or a combination of these devices. Strobes are either made of xenon tubes (most common) or recently LEDs.
  • Building safety interfaces: This interface allows the fire alarm system to control aspects of the built environment, prepare the building for fire, and control the spread of smoke fumes by influencing air movement, lighting, process control, human transport, and availability of exits.[12]

Initiating devices

Fire alarm pull station
  • Manually actuated devices; also known as fire alarm boxes, manual pull stations, or simply pull stations, break glass stations, and (in Europe) call points. Devices for manual fire alarm activation are installed to be readily located (near the exits), identified, and operated. They are usually actuated using physical interaction, such as pulling a lever or breaking glass.
  • Automatically actuated devices can take many forms intended to respond to any number of detectable physical changes associated with fire: convected thermal energy for a heat detector, products of combustion for a smoke detector, radiant energy for a flame detector, combustion gases for a fire gas detector, and operation of sprinklers for a water-flow detector. The newest innovations can use cameras and computer algorithms to analyze the visible effects of fire and movement in applications inappropriate for or hostile to other detection methods.[13][14]

Notification appliances

File:NFPA Fire Alarm.ogg

A speaker and a remote light
A fire alarm notification appliance (Sweden)
A combined fire alarm/general alert notification appliance allows a single device to serve fire alarm and general emergency notification purposes.

Alarms can be either motorized bells or wall-mountable sounders/horns. They can also be speaker strobes that sound an alarm, followed by a voice evacuation message for clearer instructions on what to do. Fire alarm sounders can be set to certain frequencies and different tones, including low, medium, and high, depending on the country and manufacturer of the device. Most fire alarm systems in Europe sound like a siren with alternating frequencies. Fire alarm electronic devices are known as horns in the United States and Canada and can be continuous or set to different codes. Fire alarm warning devices can also be set to different volume levels.

  • Notification Appliances utilize audible, visible, tactile, textual or even olfactory stimuli (odorizer)[15][16] to alert the occupants of the need to evacuate or take action in the event of a fire or other emergency. Evacuation signals may consist of simple appliances that transmit uncoded information, coded appliances that transmit a predetermined pattern, and or appliances that transmit audible and visible textual information such as live or prerecorded instructions, and illuminated message displays. Some Notification appliances are combined fire alarm/general emergency notification appliances, allowing fire and general emergency notifications from a single device.
  • In the United States, fire alarm evacuation signals generally consist of a standardized audible tone, with visual notification in all public and common-use areas. Emergency signals are intended to be distinct and understandable to avoid confusion with other signals.

As per NFPA 72, 18.4.2 (2010 Edition) Temporal Code 3 is the standard audible notification in a modern system. It consists of a repeated three-pulse cycle (0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off). Voice Evacuation is the second most common audible in a modern system. Legacy systems, typically found in older schools and buildings, have used continuous tones alongside other audible schemas.

  • In the United Kingdom, fire alarm evacuation signals generally consist of a two-tone siren with visual notification in all public and common-use areas. Some fire alarm devices have an alert signal which is generally used for schools for lesson changes, the start of morning break, the end of morning break, the start of lunch break, the end of lunch break, and when the school day is over.
  • Audible textual appliances that are employed as part of a fire alarm system that includes Emergency Voice Alarm Communications (EVAC) capabilities. High-reliability speakers notify the occupants of the need for action concerning a fire or other emergency. These speakers are employed in large facilities where general undirected evacuation is impracticable or undesirable. The signals from the speakers are used to direct the occupant's response. The system may be controlled from one or more locations within the building, known as Fire Wardens Stations or from a single location designated as the building Fire Command Center. The fire alarm system automatically actuates speakers in a fire event. Following a pre-alert tone, selected groups of speakers may transmit one or more prerecorded messages directing the occupants to safety. These messages may be repeated in one or more languages. Trained personnel activating and speaking into a dedicated microphone can suppress the replay of automated messages to initiate or relay real-time voice instructions.[17]

Emergency voice alarm communication systems

  • Some fire alarm systems utilize emergency voice alarm communication systems (EVAC)[18] to provide prerecorded and manual voice messages. Voice alarm systems are typically used in high-rise buildings, arenas, and other large "defend-in-place" occupancies such as hospitals and detention facilities where total evacuation is difficult to achieve.[citation needed]
  • Voice-based systems allow response personnel to conduct orderly evacuation and notify building occupants of changing event circumstances.[citation needed]
  • In highrise buildings, different evacuation messages may be played on each floor, depending on the location of the fire. The floor the fire is on along with ones above it may be told to evacuate while floors much lower may be asked to stand by.[citation needed]

Mass notification systems/Emergency communication systems

New codes and standards introduced around 2010, especially the new UL Standard 2572, the US Department of Defense's UFC 4-021-01 Design and O&M Mass Notification Systems, and NFPA 72 2010 edition Chapter 24, have led fire alarm system manufacturers to expand their systems voice evacuation capabilities to support new requirements for mass notification including support for multiple types of emergency messaging (i.e., inclement weather emergency, security alerts, amber alerts). The major requirement of a mass notification system are to provide prioritized messaging according to the local facilities' emergency response plan. The emergency response team must prioritize potential emergency events at the site. The fire alarm system must support the promotion and demotion of notifications based on this emergency response plan. Emergency Communication Systems also have requirements for visible notification in coordination with any audible notification activities to meet needs of the Americans with Disabilities Act. Many manufacturers have tried to certify their equipment to meet these new and emerging standards. Mass notification system categories include the following:

  • Tier 1 systems are in-building and provide the highest level of survivability
  • Tier 2 systems are out of the building and provide the middle level of survivability
  • Tier 3 systems are "At Your Side" and provide the lowest level of survivability

Mass notification systems often extend the notification appliances of a standard fire alarm system to include PC-based workstations, text-based digital signage, and a variety of remote notification options including email, text message, RSS feed, or IVR-based telephone text-to-speech messaging.

Residential Fire Systems

Residential Fire Alarm Systems are also common place. Residential system code is a lot less strict then in commercial buildings. Typically residential fire alarm systems are installed as part of a security systems. In the United States, a residential fire alarm system is required if more than 12 smoke detectors are needed.[19] Residential Systems are a lot less complex then commercial systems and have few parts compared to commercial systems.

Building safety interfaces

Coded fire alarm pull station below a 10-inch (25 cm) bell
  • Magnetic smoke door holders/retainers: wall-mounted solenoids or electromagnets controlled by a fire alarm system or detection component that magnetically secures spring-loaded self-closing smoke-tight doors in the open position. Designed to demagnetize to allow automatic closure of the door on command from the fire control or upon failure of the power source, interconnection, or controlling element. Stored energy in the form of a spring or gravity can then close the door to restrict the passage of smoke from one space to another to maintain a tenable atmosphere on either side of the door during evacuation and firefighting efforts in buildings. Electromagnetic fire door holders can be hard-wired into the fire panel, radio-controlled, triggered by radio waves from a central controller connected to a fire panel, or, acoustic, which learns the sound of the fire alarm and releases the door upon hearing this exact sound.[20]
  • Duct-mounted smoke detection: smoke detection mounted in such a manner as to sample the airflow through ductwork and other plenums fabricated explicitly for the transport of environmental air into conditioned spaces. Interconnection to the fan motor control circuits is intended to stop air movement, close dampers and generally prevent the recirculation of toxic smoke and fumes from fire into occupiable spaces.
  • Emergency elevator service: activation of automatic initiating devices associated with elevator operation is used to initiate emergency elevator functions, such as the recall of associated elevator cab(s). The recall will cause the elevator cabs to return to the ground level for use by fire service response teams and to ensure that cabs do not return to the floor of fire incidence, in addition, to prevent people from becoming trapped in the elevators. Phases of operation include primary recall (typically the ground level), alternate/secondary recall (typically a floor adjacent to the ground level—used when the initiation occurred on the primary level), illumination of the "fire hat" indicator when an alarm occurs in the elevator hoistway or associated control room, and in some cases shunt trip (disconnect) of elevator power (generally used where the control room or hoistway is protected by fire sprinklers).
  • Public address rack (PAR): an audio public address rack shall be interfaced with a fire alarm system, by adding a signaling control relay module to either the rack power supply unit, or the main amplifier driving this rack. The purpose is to "mute" the BGM (background music) of this rack in case of an emergency in case of a fire initiating the true alarm.

British fire alarm system categories

Fire alarm systems in non-domestic premises are generally designed and installed in accordance with the guidance given in BS 5839 Part 1. There are many types of fire alarm systems, each suited to different building types and applications. A fire alarm system can vary dramatically in price and complexity, from a single panel with a detector and sounder in a small commercial property to an addressable fire alarm system in a multi-occupancy building.

BS 5839 Part 1 categorizes fire alarm systems as:[21]

  • "M" manual system (no automatic fire detectors so the building is fitted with call points and sounders).
  • "L" automatic systems intended for the protection of life.
  • "P" automatic systems intended for the protection of property.

Categories for automatic systems are further subdivided into L1 to L5 and P1 to P2.

M Manual systems, e.g., handbells, gongs, etc. These may be purely manual or manual electric, the latter may have call points and sounders. They rely on the occupants of the building discovering the fire and acting to warn others by operating the system. Such systems form the basic requirement for places of employment with no sleeping risk.
P1 The system is installed throughout the building—the objective is to call the fire brigade as early as possible to minimize any damage caused by the fire. Small low-risk areas can be excepted such as toilets and cupboards less than one square meter (11 sq ft).
P2 Detection should be provided in parts of the building where the risk of ignition is high and/or the contents are precious. Category 2 systems provide fire detection in specified parts of the building where there is either high risk or where business disruption must be minimized.
L1 A category L1 system is designed for the protection of life and which has automatic detectors installed throughout all areas of the building (including roof spaces and voids) to provide the earliest possible warning. A category L1 system is likely to be appropriate for the majority of residential care premises. In practice, detectors should be placed in nearly all spaces and voids. With category 1 systems, the whole of a building is covered apart from minor exceptions.
L2 A category L2 system designed for the protection of life and which has automatic detectors installed in escape routes, rooms adjoining escape routes and high-hazard rooms. In medium-sized premises (sleeping no more than ten residents), a category L2 system is ideal. These fire alarm systems are identical to an L3 system but with additional detection in an area with a high chance of ignition (e.g., kitchen) or where the risk to people is particularly increased (e.g., sleeping risk).
L3 This category is designed to give early warnings to everyone. Detectors should be placed in all escape routes and all rooms that open onto escape routes. Category 3 systems provide more extensive cover than Category 4. The objective is to warn the occupants of the building early enough to ensure that all can exit the building before escape routes become impassable.
L4 Category 4 systems cover escape routes and circulation areas only. Therefore, detectors will be placed in escape routes, although this may not be suitable depending on the risk assessment or if the size and complexity of a building are increased. Detectors might be sited in other areas of the building, but the objective is to protect the escape route.
L5 This is the "all other situations" category, e.g., computer rooms, which may be protected with an extinguishing system triggered by automatic detection. Category 5 systems are the "custom" category and relate to some special requirements that any other category cannot cover.

Zoning

An important consideration when designing fire alarms is that of individual zones. The following recommendations are found in BS 5839 Part 1:

  • A single zone should not exceed 2,000 square meters (22,000 sq ft) in floor space.
  • Where addressable systems are in place, two faults should not remove protection from an area greater than 10,000 square meters (110,000 sq ft).
  • A building may be viewed as a single zone if the floor space is less than 300 square meters (3,200 sq ft).
  • Where the floor space exceeds 300 square meters (3,200 sq ft) then all zones should be restricted to a single floor level.
  • Stairwells, lift shafts or other vertical shafts (nonstop risers) within a single fire compartment should be considered as one or more separate zones.
  • The maximum distance traveled within a zone to locate the fire should not exceed 60 meters (200 ft).

Also, the NFPA recommends placing a list for reference near the FACP showing the devices contained in each zone.

See also

References

  1. Davis, Jemma (2018-05-11). "Lift safety in the event of a fire" (in en-GB). https://www.coopersfire.com/news/lift-safety-in-the-event-of-a-fire/. 
  2. ISO 7240-14:2013 | Fire detection and alarm systems — Part 14: Design, installation, commissioning and service of fire detection and fire alarm systems in and around buildings, https://www.iso.org/standard/{{{csnumber}}}.html 
  3. "CEN Community - List of members". https://standards.cencenelec.eu/dyn/www/f?p=CEN:5. 
  4. "VdS Guidelines for Planning and Installation of Fire Protection Systems". http://vds-global.com/en/inspection-of-fire-protection-systems/richtlinien-fuer-planung-und-einbau/. 
  5. "UNI 9795:2013" (in it). http://store.uni.com/catalogo/index.php/uni-9795-2013?josso_back_to=http://store.uni.com/josso-security-check.php&josso_cmd=login_optional&josso_partnerapp_host=store.uni.com. 
  6. "NF S61-936" (in fr). https://www.boutique.afnor.org/fr-fr/norme/nf-s61936/systemes-de-securite-incendie-ssi-equipements-dalarme-pour-levacuation-ea-r/fa164538/1339. 
  7. "UNE 23007-14:2014" (in es). https://www.une.org/encuentra-tu-norma/busca-tu-norma/norma?c=N0052478. 
  8. "Fire detection and fire alarm systems for buildings - Code of practice for design, installation, commissioning, and maintenance of systems in non-domestic premises". https://shop.bsigroup.com/products/fire-detection-and-fire-alarm-systems-for-buildings-code-of-practice-for-design-installation-commissioning-and-maintenance-of-systems-in-non-domestic-premises-1/tracked-changes. 
  9. "AS 1603.4-1987 – Automatic fire detection and alarm systems - Control and indicating equipment". https://infostore.saiglobal.com/en-us/standards/as-1603-4-1987-127336_saig_as_as_268989/. 
  10. "AS 4428.1998 – Fire detection, warning, control and intercom systems - Control and indicating equipment Fire". https://infostore.saiglobal.com/en-au/standards/as-4428-1-1998-121803_saig_as_as_255619/. 
  11. "AS AS 7240.2:2018 – Fire Detection and Alarm Systems Fire detection control and indicating equipment (ISO 7240-2:2017, MOD)". https://infostore.saiglobal.com/en-us/standards/as-7240-2-2018-121088_saig_as_as_2695586/. 
  12. Mariani, Michael (April 8, 2020). "The Components Of A Commercial Fire Alarm System". https://www.cfcsystems.com/the-components-of-a-commercial-fire-alarm-system/. 
  13. Chenebert, A.; Breckon, T.P.; Gaszczak, A. (September 2011). "A Non-temporal Texture Driven Approach to Real-time Fire Detection". Proc. International Conference on Image Processing. IEEE. pp. 1781–1784. doi:10.1109/ICIP.2011.6115796. ISBN 978-1-4577-1303-3. http://www.durham.ac.uk/toby.breckon/publications/papers/chenebert11fire.pdf. Retrieved 8 April 2013. 
  14. Dunnings, A.; Breckon, T.P. (2018). "Experimentally Defined Convolutional Neural Network Architecture Variants for Non-temporal Real-time Fire Detection". Proc. International Conference on Image Processing. IEEE. http://www.durham.ac.uk/toby.breckon/publications/papers/dunnings18fire.pdf. Retrieved 9 August 2018. [yes|permanent dead link|dead link}}]
  15. National Fire Protection Association (February 2001). "Chapter 3 Fundamental Fire Protection Program and Design Elements". NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants. National Fire Protection Association. standard: Gaseous Fire Suppression Systems 3.10.7. 
  16. National Fire Protection Association (2011). "Chapter 4 Annex A". NFPA 12 Standard on Carbon Dioxide Extinguishing Systems. National Fire Protection Association. standard: A.4.5.6.2.2. 
  17. Cote, Arthur E. (March 2000). Fire Protection Handbook eighteenth edition. National Fire Protection Association. pp. 5–8. ISBN 0-87765-377-1. 
  18. NFPA 72 – National Fire Alarm and Signaling Code – 2010 Edition. National Fire Alarm Association, 2009, Page 118, Subsection 24.4.1
  19. "What's the maximum amount of hardwired smoke alarms I can install?". https://support.firstalert.com/s/article/hardwired-alarm-limits#:~:text=The%20National%20Fire%20Protection%20Association,%2C%20strobes%2C%20or%20auxiliaries).. 
  20. "Fire Door Holders - Geofire". http://www.geofire.co.uk/product-category/fire-door-holders/. 
  21. "Fire Industry Association Fact File 0058". the Fire Industry Association ("FIA"). http://www.fia.uk.com/en/info/document-summary.cfm/docid/68D292FB-A98D-4950-A66B52B86550D34B. 

External links