Engineering:Stacking factor

From HandWiki
Revision as of 17:51, 4 February 2024 by Unex (talk | contribs) (fixing)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

The stacking factor (also lamination factor or space factor[1]) is a measure used in electrical transformer design and some other electrical machines. It is the ratio of the effective cross-sectional area of the transformer core to the physical cross-sectional area of the transformer core. The two are different because of the way cores are constructed. Transformer cores are usually made up of thin metal sheets stacked in layers. The layers are laminated with varnish or other insulating material. The purpose is to reduce eddy currents in the core. The stacking factor depends on the thickness of the lamination of the steel sheets which comprise the core.

The stacking factor is usually 0.9. The stacking factor is always less than 1.

while keeping a high magnetic flux.  Since the insulator is non-ferro-magnetic, little, if any, magnetic flux is contained within it.  It is mainly in the metal sheets.  The insulation takes up a finite space, so the effective area the flux occupies is less than the physical area of the core.[2]

The stacking factor is used when calculating the magnetic flux density within the core. Because the flux is confined within a smaller area in a laminated core, the flux density is higher than it would be in a homogeneous core.[3]

Laminated cores always have a stacking factor less than unity; a stacking factor of unity implies no laminate at all. Stacking factors are typically 0.95 or higher for transformer cores[4] and machine stators.[5] However, cores made from amorphous metal have a stacking factor of around 0.8, compared to 0.96 for silicon steel.[1]

A related concept in transformer design is window space factor. This is defined as the ratio of the area occupied by the copper windings to the area of the space they pass through (the "window"). The higher the operational voltage of the transformer, the smaller this ratio needs to be in order to provide more space for insulation.[6]

References

  1. 1.0 1.1 Barry W. Kennedy, Energy Efficient Transformers, p. 140, McGraw Hill Professional, 1998 ISBN:0070342881.
  2. "Laminated cores simulation", Quick Field, accessed and archived 29 September 2019.
  3. I. Govind G Vishnu, ', p. 12, Vels University .
  4. W.G. Hurley, W.H. Wölfle, Transformers and Inductors for Power Electronics, p. 109, John Wiley & Sons, 2013 ISBN:1118544676.
  5. Jacek F. Gieras, Rong-Jie Wang, Maarten J. Kamper, Axial Flux Permanent Magnet Brushless Machines, p. 81, Springer Science & Business Media, 2008 ISBN:1402082274.
  6. M. V. Deshpande, Design and Testing of Electrical Machines, p. 119, PHI Learning,, 2010 ISBN:8120336453