Current loop

From HandWiki
Short description: Electrical signalling scheme


In electrical signalling an analog current loop is used where a device must be monitored or controlled remotely over a pair of conductors. Only one current level can be present at any time.

A major application of current loops is the industry de facto standard 4–20 mA current loop for process control applications, where they are extensively used to carry signals from process instrumentation to proportional–integral–derivative (PID) controllers, supervisory control and data acquisition (SCADA) systems, and programmable logic controllers (PLCs). They are also used to transmit controller outputs to the modulating field devices such as control valves. These loops have the advantages of simplicity and noise immunity, and have a large international user and equipment supplier base. Some 4–20 mA field devices can be powered by the current loop itself, removing the need for separate power supplies, and the "smart" Highway Addressable Remote Transducer (HART) Protocol uses the loop for communications between field devices and controllers. Various automation protocols may replace analog current loops, but 4–20 mA is still a principal industrial standard.

Process control 4–20 mA loops

Showing the evolution of analogue control loop signalling from the pneumatic era to the electronic era
Example of current loops used for sensing and control transmission. Specific example of a smart valve positioner is shown.

In industrial process control, analog 4–20 mA current loops are commonly used for electronic signalling, with the two values of 4 and 20 mA representing 0–100% of the range of measurement or control. These loops are used both for carrying sensor information from field instrumentation and carrying control signals to the process modulating devices, such as a valve.

The key advantages of the current loop are:

  • The loop can often power the remote device, with power supplied by the controller, thus removing need for power cabling. Many instrumentation manufacturers produce 4–20 mA sensors which are "loop powered".
  • The "live" or "elevated" zero of 4 mA allows powering of the device even with no process signal output from the field transmitter.
  • The accuracy of the signal is not affected by voltage drop in the interconnecting wiring.
  • It has high noise immunity, as it is low-impedance circuit, usually through twisted-pair conductors.
  • It is self-monitoring; currents less than 3.8 mA or more than 20.5 mA are taken to indicate a fault.[1]
  • It can be carried over long cables up to the limit of the resistance for the voltage used.
  • Inline displays can be inserted and powered by the loop, as long as total allowable loop resistance is not exceeded.
  • Easy conversion to voltage using a resistor.
  • Loop-powered "I to P" (current to pressure) converters can convert the 4–20 mA signal to a 3–15 psi pneumatic output for control valves, allowing easy integration of 4–20 mA signals into existing pneumatic plant.

Field instrumentation measurements include pressure, temperature, level, flow, pH or other process variables. A current loop can also be used to control a valve positioner or other output actuator. Since input terminals of instruments may have one side of the current loop input tied to the chassis ground (earth), analog isolators may be required when connecting several instruments in series.

The relationship between current value and process variable measurement is set by calibration, which assigns different ranges of engineering units to the span between 4 and 20 mA. The mapping between engineering units and current can be inverted, so that 4 mA represents the maximum and 20 mA the minimum.

Active and passive devices

Depending on the source of current for the loop, devices may be classified as active (supplying or "sourcing" power) or passive (relying on or "sinking" loop power). For example, a chart recorder may provide loop power to a pressure transmitter. The pressure transmitter modulates the current on the loop to send the signal to the strip chart recorder, but does not in itself supply power to the loop and so is passive. Another loop may contain two passive chart recorders, a passive pressure transmitter, and a 24 V battery (the battery is the active device). Note that a 4-wire instrument has a power-supply input separate from the current loop.

Panel mount displays and chart recorders are commonly termed "indicator devices" or "process monitors". Several passive indicator devices may be connected in series, but a loop must have only one transmitter device and only one power source (active device).

Evolution of analogue control signals

Control valve with pneumatic diaphragm actuator and "smart" 4–20 mA positioner which will also feed back the actual valve position and status over the current loop

The 4–20 mA convention was born in the 1950s out of the earlier highly successful 3–15 psi pneumatic control signal standard, when electronics became cheap and reliable enough to emulate the older standard electrically. The 3–15 psi standard had the same features of being able to power some remote devices, and have a "live" zero. However, the 4–20 mA standard was better suited to the electronic controllers being developed at the time.

The transition was gradual and has extended into the 21st century, due to the huge installed base of 3–15 psi devices. As the operation of pneumatic valves over motorised valves has many cost and reliability advantages, pneumatic actuation is still an industry standard. To allow the construction of hybrid systems, where the 4–20 mA is generated by the controller, but allows the use of pneumatic valves, a range of current to pressure (I to P) converters are available from manufacturers. These are usually local to the control valve and convert 4–20 mA to 3–15 psi (or 0.2–1.0 bar). This signal is then fed to the valve actuator or, more commonly, a pneumatic positioner. The positioner is a dedicated controller which has a mechanical linkage to the actuator movement. This ensures that problems of friction are overcome and the valve control element moves to the desired position. It also allows the use of higher air pressures for valve actuation.

With the development of cheap industrial micro-processors, "smart" valve positioners have become available since the mid-1980s and are very popular for new installations. These include an I to P converter, plus valve position and condition monitoring. These latter are fed back over the current loop to the controller, using protocols such as HART.

Long circuits

Analog current loops were historically occasionally carried between buildings by dry pairs in telephone cables leased from the local telephone company. 4–20 mA loops were more common in the days of analog telephony. These circuits require end-to-end direct current (DC) continuity, and unless a dedicated wire pair was hardwired, their use ceased with the introduction of semiconductor switching. DC continuity is not available over a microwave radio, optical fibre, or a multiplexed telephone circuit connection. Basic DC circuit theory shows that the current is the same all along the line. It was common to see 4–20 mA circuits that had loop lengths in miles or circuits working over telephone cable pairs that were longer than ten thousand feet end-to-end. There are still legacy systems in place using this technology. In Bell System circuits, voltages up to 125 VDC were employed.

Discrete control

Discrete control functions can be represented by discrete levels of current sent over a loop. This would allow multiple control functions to be operated over a single pair of wires. Currents required for a specific function vary from one application or manufacturer to another. There is no specific current that is tied to a single meaning. It is almost universal that 0 mA indicates the circuit has failed. In the case of a fire alarm, 6 mA could be normal, 15 mA could mean a fire has been detected, and 0 mA would produce a trouble indication, telling the monitoring site the alarm circuit had failed. Some devices, such as two-way radio remote control consoles, can reverse the polarity of currents and can multiplex audio onto a DC current.

These devices can be employed for any remote control need a designer might imagine. For example, a current loop could actuate an evacuation siren or command synchronized traffic signals.

Two-way radio use

A Motorola T-1300 series remote control is built in a telephone housing. The dial is replaced with a speaker and volume control. This remote control uses a two-wire circuit to control a base station.

Current loop circuits are one possible way used to control radio base stations at distant sites. The two-way radio industry calls this type of remote control DC remote. This name comes from the need for DC circuit continuity between the control point and the radio base station. A current loop remote control saves the cost of extra pairs of wires between the operating point and the radio transceiver. Some equipment, such as the Motorola MSF-5000 base station, uses currents below 4 mA for some functions. An alternative type, the tone remote, is more complex but requires only an audio path between control point and base station.[2]

For example, a taxi dispatch base station might be physically located on the rooftop of an eight-story building. The taxi company office might be in the basement of a different building nearby. The office would have a remote control unit that would operate the taxi company base station over a current loop circuit. The circuit would normally be over a telephone line or similar wiring. Control function currents come from the remote control console at the dispatch office end of a circuit. In two-way radio use, an idle circuit would normally have no current present.

In two-way radio use, radio manufacturers use different currents for specific functions. Polarities are changed to get more possible functions over a single circuit. For example, imagine one possible scheme where the presence of these currents cause the base station to change state:

  • no current means receive on channel 1, (the default).
  • +6 mA might mean transmit on channel 1
  • −6 mA might mean stay in receive mode but switch to channel 2. So long as the −6 mA current were present, the remote base station would continue to receive on channel 2.
  • −12 mA might command the base station to transmit on channel 2.

This circuit is polarity-sensitive. If a telephone company cable splicer accidentally reversed the conductors, selecting channel 2 would lock the transmitter on.

Each current level could close a set of contacts, or operate solid-state logic, at the other end of the circuit. That contact closure caused a change of state on the controlled device. Some remote control equipment could have options set to allow compatibility between manufacturers. That is, a base station that was configured to transmit with a +18 mA current could have options changed to (instead) make it transmit when +6 mA was present.

In two-way radio use, AC signals were also present on the circuit pair. If the base station were idle, receive audio would be sent over the line from the base station to the dispatch office. In the presence of a transmit command current, the remote control console would send audio to be transmitted. The voice of the user in the dispatch office would be modulated and superimposed over the DC current that caused the transmitter to operate.

See also

References

  1. NAMUR standard NE 043 "Standardisation of the Signal Level for the Failure Information of Digital Transmitters".
  2. US patent 6950653 "Scanning tone remote adapter for land-mobile radio dispatch for use with dispersed dispatch stations" (The patent does not describe this tone remote but confirms the use of the phrase to describe this system of signaling.)

Further reading

  • Lipták, Béla G. Instrumentation Engineers' Handbook. Process Measurement and Analysis. CRC Press. 2003. HB. ISBN:0-8493-1083-0

External links