Water usage effectiveness
Water Usage Effectiveness (WUE) is a sustainability metric created by The Green Grid in 2011 to measure the amount of water used by datacenters to cool their IT assets.[1][2]
Definition
The unit is ,[3] or, equivalently, .[4]
The standard ISO/IEC 30134-9:2022[5] gives more context for accurate measure, as well as specific WUE categories and various WUE derivatives.
Typical values
The WUE is a positive number. It can be 0 L/kWh (with air cooling) or up to 2.5 L/kWh (with evaporative cooling).[4]
Facebook published a WUE of 0.22 L/kWh for their datacenter of Prineville, Oregon for the second quarter of 2012.[2]
For the year 2025 Equinix reports a global WUE of 0.91 L/kWh for all their datacenters, and a WUE of 1.41 L/kWh for sites using evaporative cooling.[6]
Other metrics
WUE is less widespread than the Power usage effectiveness (PUE), but is becoming more publicized by data center operators due to ESG considerations and/or due to water scarcity.[4]
According to Equinix,[4] PUE and WUE are partially opposites: with evaporative cooling the WUE increases and the PUE decreases, and with air cooling the WUE decreases (or is zero) but the PUE increases. The cooling technology of a given datacenter may be dependent on the region (and other considerations), and may be a mix of different technologies, possibly activated differently depending on the season.
See also
- Power usage effectiveness (PUE)
- Data center infrastructure efficiency
- Performance per watt
- Green power usage effectiveness
- Green computing
- IT energy management
References
- ↑ "'Green Grid 'WP#35-Water Usage Effectiveness (WUE™): A Green Grid Data Center Sustainability Metric', retrieved 4 September 2015". http://www.thegreengrid.org/en/Global/Content/white-papers/WUE.
- ↑ 2.0 2.1 DataCenterKnowledge.com, Data Center Water Use Moves to the Forefront, retrieved 4 September 2015
- ↑ "WUE (water usage effectiveness) definition". https://searchdatacenter.techtarget.com/definition/WUE-water-usage-effectiveness.
- ↑ 4.0 4.1 4.2 4.3 "What Is Water Usage Effectiveness (WUE) in Data Centers?". https://blog.equinix.com/blog/2024/11/13/what-is-water-usage-effectiveness-wue-in-data-centers/.
- ↑ "ISO/IEC 30134-9:2022 Information technology — Data centres key performance indicators — Part 9: Water usage effectiveness (WUE)". 2022-03-01. https://www.iso.org/obp/ui/en/#iso:std:iso-iec:30134:-9:ed-1:v1:en.
- ↑ Equinix (2025) (PDF). Sustainability Report 2025 (Report). p. 26. https://delivery-p112322-e1154416.adobeaemcloud.com/adobe/assets/deliver/urn:aaid:aem:116e6fc1-6217-4132-8fcf-1dc7096396df/Equinix-Inc_2025_Sustainability-Report.pdf. Retrieved 2026-07-31.