Swing equation

From HandWiki
Short description: Differential equation in a power system

A power system consists of a number of synchronous machines operating synchronously under all operating conditions. Under normal operating conditions, the relative position of the rotor axis and the resultant magnetic field axis is fixed. The angle between the two is known as the power angle, torque angle, or rotor angle. During any disturbance, the rotor decelerates or accelerates with respect to the synchronously rotating air gap magnetomotive force, creating relative motion. The equation describing the relative motion is known as the swing equation, which is a non-linear second order differential equation that describes the swing of the rotor of synchronous machine. The power exchange between the mechanical rotor and the electrical grid due to the rotor swing (acceleration and deceleration) is called Inertial response.

Derivation

A synchronous generator is driven by a prime mover. The equation governing the rotor motion is given by:[1] Jd2θmdt2=Ta=TmTe, where:

  • J is the total moment of inertia of the rotor mass in kg-m2
  • θm is the angular position of the rotor with respect to a stationary axis in radians (rad)
  • t is time in seconds (s)
  • Ta is the net accelerating torque, in N-m
  • Tm is the mechanical torque supplied by the prime mover in N-m
  • Te is the electrical torque output of the alternator in N-m

Neglecting losses, the difference between the mechanical and electrical torque gives the net accelerating torque Ta. In the steady state, the electrical torque is equal to the mechanical torque and hence the accelerating power is zero. During this period the rotor moves at synchronous speed ωs in rad/s. The electric torque Te corresponds to the net air-gap power in the machine and thus accounts for the total output power of the generator plus |I|2R losses in the armature winding.[2]

The angular position θ is measured with a stationary reference frame. Representing it with respect to the synchronously rotating frame gives: θm=ωsmt+δm, where the mechanical power angle δm is the angular position with respect to the synchronously rotating reference frame. The derivative of the above equation with respect to time is: dθmdt=ωsm+dδmdt. The above equations show that the rotor angular speed is equal to the synchronous speed only when dδm/dt is equal to zero. Therefore, the term dδm/dt represents the deviation of the rotor speed from synchronism in rad/s.

By taking the second order derivative of the above equation it becomes: d2θmdt2=d2δmdt2. Substituting the above equation in the equation of rotor motion gives: Jd2δmdt2=Ta=TmTe. Multiplying both sides by the angular velocity of the rotor, given by ωm=dθmdt, results in Jωmd2δmdt2=Pa=PmPe, where Pa, Pm and Pe respectively are the accelerating, mechanical and electrical (active) power in Watt (W). Intuitivley, the equation can also be derived by taking the time derivative of the rotational energy.

The coefficient Jωm is the angular momentum of the rotor at synchronous speed ωsm. In machine data supplied for stability studies this coefficient is often denoted by M and called the inertia constant of the machine. In practice, ωm does not differ significantly from synchronous speed when the machine is in steady state ωsm; allowing for another constant of inertia:[3] H=12Jωsm2Srated=12MωsmSrated=stored kinetic energy in mega joules at synchronous speedmachine rating in MVA, where Srated is the three phase rating of the machine in MVA. Substituting in the above equation 2HSratedωsm2ωmd2δmdt2=PmPe=Pa. Since Pm, Pe and Pa in the machine data are given in MW, dividing them by the generator MVA rating gives these quantities in per unit. Dividing the above equation on both sides by Srated gives

2Hωsd2δdt2=PmPe=Pa per unit

with the electrical power angle and electrical angular velocity given by δ=p2δm,ω=p2ωm,ωs=p2ωsm, where p is the number of poles of the synchronous machine.

The above equation describes the behaviour of the rotor dynamics and hence is known as the swing equation. The angle δ is that of the internal EMF (E) of the synchronous generator and dictates the amount of power that can be transferred. This angle is therefore called the power angle. Neglecting the machine's resistive losses, the corresponding power angle equation is:[4] Pe=Pmaxsin(δ)=3|V||E|Xsin(δ), where X is the machine reactance and V the system (i.e. grid) voltage.[5] The angle δ is also referred to as the torque angle as the electrical torque Te can be derived from this equation as[6] Te=Peωm=3|V||E|ωmXsin(δ). Hence, for synchronous machines the swing equation is a non-linear function of δ and can be solved numerically using, e.g., the fourth-order Runge-Kutta algorithm. When δ is small, the equation can be linearized as PePmaxδ.[7]

See also

Notes

  1. Grainger & Stevenson 1994, pp. 698-702.
  2. Umans 2013, pp. 263-264.
  3. Saadat 1999, pp. 462-463.
  4. Grainger & Stevenson 1994, pp. 709-712.
  5. Schavemaker & van der Sluis 2008, pp. 71-74.
  6. Chapman 2011, chpt. 4.6 Power and Torque in Synchronous Generators.
  7. Guru & Hiziroǧlu 2001, pp. 648-651.

References